ResidualCurrentCircuitBreak


Přisuzování:
Obrázek je označen jako „Vyžadováno uvedení zdroje“ (Attribution Required), ale nebyly uvedeny žádné informace o přiřazení. Při použití šablony MediaWiki pro licence CC-BY byl pravděpodobně parametr atribuce vynechán. Autoři zde mohou najít příklad pro správné použití šablon.
Formát:
350 x 171 Pixel (23074 Bytes)
Popis:
photo of electrical Residual-Current Circuit Breaker
  1. incoming terminals
  2. outgoing terminals
  3. reset button
  4. contact
  5. solenoid
  6. sense coil
  7. sense circuitry
  8. test button
  9. test wire


The incoming supply and the neutral conductors are connected to the terminals at (1) and the outgoing load conductors are connected to the terminals at (2). The earth conductor (not shown) is connected through from supply to load uninterrupted.

When the reset button (3) is pressed the contacts ((4) and hidden behind (5)) close, allowing current to pass. The solenoid (5) keeps the contacts closed when the reset button is released.

The sense coil (6) is a differential current transformer which surrounds (but is not electrically connected to) the live and neutral conductors. In normal operation, all the current down the live conductor returns up the neutral conductor. The currents in the two conductors are therefore equal and opposite and cancel each other out.

Any fault to earth (for example caused by a person touching a live component in the attached appliance) causes some of the current to take a different return path which means there is an imbalance (difference) in the current in the two conductors (single phase case), or, more generally, a nonzero sum of currents from among various conductors (for example, three phase conductors and one neutral conductor).

This difference causes a current in the sense coil (6) which is picked up by the sense circuitry (7). The sense circuitry then removes power from the solenoid (5) and the contacts (4) are forced apart by a spring, cutting off the electricity supply to the appliance.

The device is designed so that the current is interrupted in a fraction of a second, greatly reducing the chances of a dangerous electric shock being received.

The test button (8) allows the correct operation of the device to be verified by passing a small current through the orange test wire (9). This simulates a fault by creating an imbalance in the sense coil. If the RCD does not trip when this button is pressed then the device must be replaced.
Licence:
Credit:
Vlastní dílo
Sdílet obrázek:
Facebook   Twitter   Pinterest   WhatsApp   Telegram   E-Mail
Více informací o licenci na obrázek naleznete zde. Poslední aktualizace: Tue, 28 Nov 2023 15:21:56 GMT

Relevantní obrázky


Relevantní články

Proudový chránič

Proudový chránič je elektrický přístroj, který chrání obsluhu před nebezpečným dotykovým napětím i proti požáru. Odpojí chráněný elektrický obvod, pokud část přitékajícího proudu uniká mimo obvod, například při poškození izolace nebo při dotyku člověka. Proudový chránič neomezuje procházející nadměrný proud, k tomu slouží elektrický jistič. Od roku 2019 je jeho použití povinné ve všech nových běžných elektrických instalacích. Používá se v uzemňovací soustavě TN-S nebo TN-C-S a sítích TT. Pokud požadujeme zvýšenou bezpečnost, lze jej použít i v síti IT. V síti TN-C jej použít nelze. Proto se již takové sítě nesmí v rámci EU nově budovat ani je vytvářet při rekonstrukcích stávajících elektroinstalací. .. pokračovat ve čtení